iSMA-B-4U4A-H

I/O module with Modbus RTU/ASCII or BACnet MSTP communication- 4UI and 4DO with hand operating
£265.66
Ship to
*
*
Shipping Method
Name
Estimated Delivery
Price
No shipping options

The module iSMA-B-4U4A-H has 4xUI (Universal Inputs) and 4xAO (Analog Outputs). UI can work in 5 different modes: temperature, voltage, current, resistance, dry contact. AO are 0-10 V DC with max. 20 mA load allow direct control of relays (12 V DC) or SSR with PWM support.

The module is factory-equipped with the two most popular open communication protocols: Modbus ASCII/RTU and BACnet MSTP, which are selected using DIP switches.

Addressing the modules is via rotary switches, which facilitates and accelerates the process of commissioning the system.

Built-in mini USB allows for initial configuration of the unit without power supply.

Specifications
4x Universal Inputs (4UI)

All universal inputs have 16-bit resolution which support the following types of inputs:

  • Temperature input support the following types of sensors: 10K3A1, 10K4A1, Carel 10K, 20K6A1, 2.2K3A1, 3K3A1, 30K6A1, SIE1, TAC1, SAT1, Pt1000, Ni1000
    For sensor Pt1000 and Ni1000 use only 16bit resolution
  • Voltage input 0-10 V DC: input resistance 100 kΩ accuracy ±0,1% measurement resolution 3 mV @ 12bit and 1 mV @ 16bit
  • Current input 0-20 mA
  • Resistive input 0-1000 kΩ: measurement resolution for 20 kΩ load 20 Ω @ 12bit and 1 Ω @ 16bit
  • Dry contact input
4x Analog Outputs (4AO)

All analog outputs are equipped with 12bit ADC provides 10 mV resolution and accuracy less than ±0,5%. They support the following output types:

  • Output 0-10 V DC maximum load up to 20 mA
  • PWM: 0,01 Hz, 0,1 Hz, 1 Hz, 10 Hz, 100 Hz
Platform
  • Cortex-M3
Communication
  • Interface RS485 half duplex
  • Up to 99 devices on the bus
  • Protocols: Modbus or BACnet
  • Baud rate: 2400 to 115200 bps
Power supply
  • 24 V AC/DC
Housing
  • Dimension: 37x110x62 mm (1.457 x4.331×2.441 in)
  • Construction: plastic, self-extinguishing (PC/ABS)
  • DIN rail mounting (DIN EN 50022 norm)
  • Cooling: internal air circulation
Environments
  • Operating temperature: -10°C to 50°C (14°F to 122°F)
  • Storage temperature: -40°C to 85°C (-40°F to 185°F)
  • Relative humidity: 5 to 95%, no condensation
  • Ingress Protection Rating: IP40 – for indoor installation