iSMA-B-8U-IP

I/O module with Modbus TCP/IP (with built in Modbus Gateway to RS485) or BACnet IP communication- 8UI
Manufacturer: iSMA Controlli
Delivery date: 1-2 days
£316.89
Ship to
*
*
Shipping Method
Name
Estimated Delivery
Price
No shipping options

The module iSMA-B-8U-IP has 8xUI (Universal Inputs).  UI can work in 5 different modes: temperature, voltage, current, resistance, dry contact.

The module is factory-equipped with the two most popular open communication protocols: Modbus TCP/IP and BACnet IP, which are selected using DIP switches.

Built-in Modbus Gateway TCP/IP to Modbus ASCII/RTU, enabling you to connect additional modules/devices that communicate via Modbus RS485.

Addressing the modules is via rotary switches, which facilitates and accelerates the process of commissioning the system.

Built-in mini USB allows for initial configuration of the unit without power supply.

Specifications

8x Universal Inputs (8UI)

All universal inputs have 16-bit resolution which support the following types of inputs:

  • Temperature input support the following types of sensors: 10K3A1, 10K4A1, Carel 10K, 20K6A1, 2.2K3A1, 3K3A1, 30K6A1, SIE1, TAC1, SAT1, Pt1000, Ni1000
    For sensor Pt1000 and Ni1000 use only 16bit resolution
  • Voltage input 0-10 V DC: input resistance 100 kΩ accuracy ±0,1% measurement resolution 3 mV @ 12bit and 1 mV @ 16bit
  • Current input 0-20 mA
  • Resistive input 0-1000 kΩ: measurement resolution for 20 kΩ load 20 Ω @ 12bit and 1 Ω @ 16bit
  • Dry contact input

Platform

  • Cortex-M3

Power supply

  • 24 V AC/DC

Communication

  • Interface RS485 half duplex
  • 1 x Fast Ethernet
  • Up to 99 devices on the bus
  • Protocols: Modbus or BACnet
  • Baud rate: 2400 to 115200 bps

Housing

  • Dimension: 37x110x62 mm (1.457 x4.331×2.441 in)
  • Construction: plastic, self-extinguishing (PC/ABS)
  • DIN rail mounting (DIN EN 50022 norm)
  • Cooling: internal air circulation

Environments

  • Operating temperature: -10°C to 50°C (14°F to 122°F)
  • Storage temperature: -40°C to 85°C (-40°F to 185°F)
  • Relative humidity: 5 to 95%, no condensation
  • Ingress Protection Rating: IP40 – for indoor installation
  Datasheet

  Installation Instruction

  Manual BACnet

  Manual Modbus